We have to multiply the actual load current times by 1.25 (2017 NEC: 210.20(A)).
NEC 210.20(A) Continuous and Noncontinuous Loads:
The rating of the overcurrent device must be no less than the noncontinuous load plus 125 percent of the continuous load when a branch circuit delivers continuous loads or any combination of continuous and noncontinuous loads.
With one exception, the ampere rating of the overcurrent device may not be less than the total of the continuous load and the noncontinuous load when the assembly, including the overcurrent devices safeguarding the branch circuit(s), is rated for operation at 100% of its rating.
To learn more about this, have a look at this example:
https://brainly.com/question/29095477
#SPJ4